In-House Testing Facilities & Quality Inspection
Every switchboard manufactured by Shivam Electricals undergoes stringent stage-wise testing in our dedicated test bay before factory release, conforming strictly to IS 8623 (Part I) and IEC 61439 standards.

Calibrated Testing Infrastructure
On the strength of over two decades of engineering experience, Shivam Electricals has always sought to produce switchboards complying with national and international safety codes.
Our in-house testing bay is equipped with calibrated test kits including a 2kV High Voltage Test Kit, 500V/1000V Megger Insulation Testers, Primary Current Injection Kits (up to 2000A), and Secondary Relay Calibration Units.

100% Routine Tests Conducted on Every Panel
Mandatory test protocol executed prior to client factory acceptance test (FAT) or site dispatch.
Inspection of Assembly & Wiring
IS 8623 Part 1Visual verification of component ratings, phase clearances, creepage distances, terminal numbering, and cable ferrule identification.
Continuity & Circuit Verification
IS 8623 / IEC 61439Point-to-point electrical continuity testing of all power, control, interlock, metering, and protective relay circuits.
Insulation Resistance (Megger Test)
Tested at 500V / 1000V DCMeasured between phases, phase-to-neutral, and all live conductors to earth before and after high-voltage dielectric application.
High Voltage (HV) Dielectric Test
2 kV AC for 1 MinuteHigh-voltage stress testing applied across main power circuits and control circuits to prove insulation integrity.
Type Tests per IS 8623 (Part I)
Proven switchgear designs certified for short-circuit withstand capacity and continuous thermal rise limits.
Short-Circuit Withstand Test
Verifies the mechanical and thermal strength of busbars and non-hygroscopic supports under extreme short-circuit fault conditions.
Temperature Rise Test
Monitors thermal rise across main busbars, breaker connection joints, and enclosed air to ensure full compliance with IS limits.
Dielectric Properties & Clearance Verification
Ensures adequate electrical clearances and creepage distances across compartmentalized Form 4 barriers.
Special & Relay Calibration Tests
Primary Injection Testing
High-current injection up to 2000A to verify current transformer (CT) ratios, polarity, and magnetic saturation thresholds under live loads.
Secondary Injection Testing
Precision electronic injection testing of microprocessor-based and numerical protection relays to verify pickup times and trip curve characteristics.
Electrostatic Powder Coat DFT Verification
Digital magnetic thickness gauge inspection ensuring uniform 70 to 90-micron paint film thickness after baking oven curing.
Mechanical Interlock & Defeat Checks
Rigorous verification of breaker draw-out mechanisms, door interlocks, padlocking provisions, and safety shutters.
6 Stage-Wise Quality Inspection Gates
Total Quality Management (TQM) adhered to across every production phase.
CRCA steel sheet thickness check, electrolytic purity of copper/aluminum busbars, and certified switchgear components.
Dimensional tolerance checks, burr-free shearing, precise CNC bending angles, and welded joint strength.
Chemical titration checks across degreasing, derusting, phosphating, and passivation baths.
Visual finish inspection, cross-hatch adhesion testing, and digital DFT coating thickness verification.
Torque wrench tightening of all busbar joint fasteners with torque seal marking and color-coded PVC sleeving.
High voltage 2kV test, 1000V Megger, primary/secondary injection, and client witness inspection before dispatch.
Schedule a Factory Acceptance Test (FAT)
We welcome client engineers and consultants to witness live testing of their switchboards at our Kalher test facility.