All Services
Field Engineering DivisionTurnaround: Scheduled test days (1 to 2 days per generator)Load Test Certification Document

Load Bank Testing for Standby DG Sets

Resistive and inductive load bank testing to verify standby generator cooling efficiency and avoid wet stacking.

Service Scope

Step load testing up to 100% and 110% overload, voltage regulation, frequency droop, and cooling check

Equipment Profile

Diesel Generators (DG Sets up to 2500 kVA), UPS Systems, Rotary Converters

24/7 Breakdown Hotline
Load Bank Testing for Standby DG Sets

Key Engineering Advantages & ROI

Burns unburnt carbon deposits and eliminates diesel engine wet stacking
Proves generator capacity to support full facility load during power blackouts
Verifies cooling system, thermostat, and radiator efficiency under sustained heat
Ensures compliance with commercial building and hospital safety codes

Detailed Scope & Technical Execution

Diesel generators that run only on light load exercises develop carbon buildup and "wet stacking", preventing them from delivering full power when grid failures occur. Shivam connects controlled resistive load banks to verify real-world capacity under safe testing conditions.

Standardized Step-by-Step Engineering Methodology

1
Step 1: Mobile resistive load bank positioning and heavy power cable hookup
2
Step 2: Baseline electrical, fuel, and cooling temperature measurements
3
Step 3: Step load application (25%, 50%, 75%, 100%, and 110% overload)
4
Step 4: Continuous logging of voltage, frequency, oil pressure, and exhaust temp
5
Step 5: Load rejection testing to record governor transient recovery times

Formal Engineering Deliverables

Certified Generator Load Bank Test Certificate
Step-by-Step Load vs Parameter Log Sheet
Fuel & Cooling Efficiency Summary
Schedule Field Engineers

Book Service Visit

Provide your plant location and scheduled shutdown window for rapid engineering dispatch.

Send Us a Message

Have a project in mind or inquiry? Drop your details and our team will get back to you shortly.

NABL-Traceable Calibrated Test Kits

All on-site primary/secondary injection kits, high-voltage test units, and Megger testers carry current NABL calibration certificates.

Read testing protocols